HVAC/R parts, identified and specified
What each part is, how to tell which one you have, and what to write down before you ask for a replacement. For new techs, facility maintenance staff and capable homeowners. Nothing is sold here.
ACR copper tube is sold by its outside diameter
Thermostat wire colors
- RRed24 V power from the transformer
- CBlue24 V common, the return side
- WWhiteHeat call
- YYellowCompressor, cooling call
- GGreenIndoor fan
- O/BOrangeHeat pump reversing valve
- W2BrownSecond stage or auxiliary heat
Fast answers
| Question | Short answer |
|---|---|
| Can I buy refrigerant without a card? | No. Sales are restricted to EPA Section 608 certified technicians. |
| What goes in a new residential system? | R-454B or R-32, both A2L. R-410A is being phased down. |
| Is a 16 x 25 x 1 filter really that size? | No. It usually measures about 15-1/2 x 24-1/2 x 3/4. |
| Can I use a 440 V capacitor in place of a 370 V? | Yes, if the microfarads match. Never the other way round. |
| Is a lower gauge number thicker? | Yes. 26 gauge is thicker than 30. |
| Can I use alkaline cleaner on an indoor coil? | Use a no-rinse evaporator cleaner indoors instead. |
| Which way does the motor turn? | The nameplate says, and it says which end to view from. |
Categories
- FLFilters
Nominal and actual sizes, MERV ratings, pressure drop, media depth.
- CTControls
Thermostat wire, capacitors, contactors, relays, pressure and limit switches.
- CHChemicals
Coil cleaners by pH, condensate treatments, leak detection, safety data sheets.
- CPCompressors, motors, pumps
Nameplates, PSC and ECM motors, condensate pumps, circulators.
- DSDuct and sheet metal
Gauges, flex duct, duct board, mastic, UL 181 tapes.
- EQEquipment
Split, packaged and ductless systems, ice machines, spot coolers.
- SVCertification and reclaim
EPA 608 types, refrigerant status, recover, recycle and reclaim.
- PRAll categories
The full index, the tube chart and what to bring to any counter.
- CUBefore you go to the counter
What to bring and write down, what needs a 608 card, who to contact for what.
How to use a supply counter well
A counter person can find almost any part from three things: the equipment model and serial number, the numbers printed on the old part, and the old part itself. Most wrong parts go home with people who brought none of the three. Photograph the unit data plate and the part label before you take anything apart, and bring the failed part with you.
Each category page here ends with a short list of what to write down for that kind of part, and before you go to the counter collects them in one table. The section codes on the yellow labels, such as FL2 or CT4, are the same ones in each page's index, so you can point someone to an exact table. If you are new to the trade, start with the category index, then read certification and reclaim before you touch a refrigerant circuit.